These are reference Standards of Practice. For an official copy of the
Standards go to the
TREC web site.
Index to Standards
Definitions
Scope
General limitations
Departure
Foundations
Grading and drainage
Roof covering materials
Roof structure / attic
Exterior and interior glazing
Exterior walls, doors, and windows
Interior walls, ceilings, floors, and doors
Exterior and interior glazing
Interior and exterior stairways
Fireplace and chimney
Porches, Balconies, Decks, and Carports
Service entrance and panels
Branch circuits, connected devices, and fixtures
Smoke alarms
Heating equipment
Cooling equipment
Evaporative coolers
Duct system, chases, and vents
Plumbing systems
Water heaters
Hydro-massage therapy equipment
Dishwasher
Food waste disposer
Range exhaust vent
Electric or gas ranges, cooktops, and ovens
Microwave oven
Trash compactor
Mechanical exhaust vents and bathroom heaters
Garage door operators
Doorbell and chimes
Dryer vent
Lawn irrigation
Pools and spas
Outbuildings
Outdoor cooking
Gas supplies
Private Wells
Private Sewage
Vacuums
Other Appliances
The following Standard was copied from TREC
and is subject to verification by the user. Its intent is to serve as a guide
for the Request for Interpretation process.
Standards of Practice
(a) Definitions.
top
(1) Accessible--In the reasonable
judgment of the inspector, capable of being approached, entered, or viewed
without:
(A) undue hazard to the
inspector;
(B) moving furnishings or
large, heavy, or fragile objects;
(C) using specialized tools or
procedures;
(D) disassembling items other than covers or panels
intended to be removed for inspection;
(E) damaging property; or
(F) using a ladder for portions of the inspection other
than the roof or attic space.
(2) Chapter 1102--Texas
Occupations Code, Chapter 1102.
(3) Cosmetic--Related only to
appearance or aesthetics, and not related to structural performance,
operability, or water penetration.
(4) Deficiency--A condition that,
in the inspector’s reasonable opinion, adversely and materially affects the
performance of a system or component or constitutes a hazard to life, limb, or
property as specified by these standards of practice. General deficiencies
include but are not limited to inoperability, material distress, water
penetration, damage, deterioration, missing parts, and unsuitable installation.
(5) Deficient--Reported as having
one or more deficiencies.
(6) Inspect--To look at and
examine accessible items, parts, systems, or components and report observed
deficiencies.
(7) Performance--Achievement of
an operation, function, or configuration consistent with accepted industry
practice.
(8) Report--To provide the
inspector's opinions and findings on the standard inspection report form.
(9) Specialized tools--Tools such
as thermal imaging equipment, moisture meters, gas leak detection equipment,
environmental testing equipment and devices, elevation determination devices,
and ladders capable of reaching surfaces over one story above ground surfaces.
(10) Specialized procedures--
Procedures such as environmental testing, elevation measurement, and any method
employing destructive testing that damages otherwise sound materials or
finishes.
(11) Standards of practice--
§§535.227 - 535.233 of this title.
(b) Scope.
top
(1) These standards of practice
define the minimum levels of inspection required for substantially completed
residential improvements to real property up to four dwelling units. A real
estate inspection is a limited visual survey and basic operation of the systems
and components of a building using normal controls and does not require the use
of specialized tools or procedures. The purpose of the inspection is to provide
the client with information regarding the general condition of the residence at
the time of inspection. The inspector may provide a higher level of inspection
performance than required by these standards of practice and may inspect parts,
components, and systems in addition to those described by the standards of
practice.
(2) General Requirements. The
inspector shall:
(A) operate fixed or installed
equipment and appliances listed herein in at least one mode with ordinary
controls at typical settings;
(B) visually inspect accessible
systems or components from near proximity to the systems and components, and
from the interior of the attic and crawl spaces; and
(C) complete the standard
inspection report form as required by §535.222 and §535.223 of this title.
(3)
General limitations. The inspector is not required to:
top
(A) inspect:
(i) items other than those
listed herein;
(ii) elevators;
(iii) detached structures,
decks, docks, fences, or waterfront structures or equipment;
(iv) anything buried, hidden,
latent, or concealed; or
(v) automated or programmable control
systems, automatic shut-off, photoelectric sensors, timers, clocks, metering
devices, signal lights, lightning arrestor system, remote controls, security
or data distribution systems, or solar panels;
(B) report:
(i) past repairs that appear to
be effective and workmanlike;
(ii) cosmetic or aesthetic
conditions; or
(iii) wear and tear from
ordinary use;
(C) determine:
(i) insurability, warrantability,
suitability, adequacy, capacity, reliability,
marketability, operating costs, recalls, counterfeit products, life
expectancy, age, energy efficiency, vapor barriers, thermostatic operation,
code compliance, utility sources, or manufacturer or regulatory requirements
except as specifically required by these standards;
(ii) the presence or absence of
pests, termites, or other wood-destroying insects or organisms;
(iii) the presence, absence, or
risk of asbestos, lead-based paint, mold, mildew, or any other environmental
hazard, environmental pathogen, carcinogen, toxin, mycotoxin, pollutant,
fungal presence or activity, or poison; or
(iv) types of wood or
preservative treatment and fastener compatibility;
(D) anticipate future events or
conditions, including but not limited to:
(i) decay, deterioration, or
damage that may occur after the inspection;
(ii) deficiencies from abuse,
misuse or lack of use,
(iii) changes in performance of any part,
component, or system due to changes in use or occupancy;
(iv) the consequences of the
inspection or its effects on current or future buyers and sellers;
(v) common household accidents,
personal injury, or death;
(vi) the presence of water
penetration (s); or
(vii) future performance of any
item;
(E) operate shut-off, safety,
stop, pressure, or pressure-regulating valves or items requiring the use of
codes, keys, combinations, or similar devices;
(F) designate conditions as safe;
(G) recommend or provide engineering, architectural, appraisal, mitigation,
physical surveying, realty, or other specialist services;
(H) review historical records,
installation instructions, repair plans, cost estimates, disclosure documents,
or other reports;
(I) verify sizing, efficiency, or
adequacy of the ground surface drainage system;
(J) operate recirculation or sump
pumps;
(K) remedy conditions preventing
inspection of any item;
(L) apply open flame to operate
any appliance;
(M) turn on decommissioned
equipment, systems, or utility services; or
(N) provide repair cost
estimates, recommendations, or re-inspection services.
(4) In the event of a conflict
between specific provisions and general provisions in the standards of practice,
specific provisions shall take precedence.
(5)
Departure.
top
(A) An inspector may depart
from the standards of practice only if the requirements of subparagraph (B)
are met, and:
(i) the inspector and client
agree the item is not to be inspected;
(ii) the inspector is not
qualified to inspect the item;
(iii) conditions beyond the
control of the inspector reasonably prevent inspection of an item;
(iv) the item is a common
element of a multi-family development and is not in physical contact with
the unit being inspected, such as the foundation under another building or a
part of the foundation under another unit in the same building;
(v) the inspector reasonably
determines that conditions or materials are hazardous to the health or
safety of the inspector; or
(vi) the inspector reasonably
determines that actions of the inspector may cause damage to the property.
(B) If a part, component, or
system required for inspection is not inspected, the inspector shall:
(i) advise the client at the
earliest practical opportunity that the part, component, or system will not
be inspected; and
(ii) make an appropriate
notation on the inspection report form, clearly stating the reason the part,
component, or system was not inspected.
(C) If the inspector routinely
departs from inspection of a part, system, or component, the earliest
practical opportunity for the notice required by this subsection is the first
contact with the prospect and the inspector has reason to believe that the
property being inspected has the part, system, or component the inspector
routinely does not inspect.
(c) Enforcement. Failure to
comply with the standards of practice is grounds for disciplinary action as
prescribed by Chapter 1102.
§535.228. Standards of Practice:
Minimum Inspection Requirements for Structural Systems.
(a)
Foundations. The inspector shall: top
(1) inspect slab surfaces,
foundation framing components, subflooring, and related structural components;
(2) report:
(A) the type of foundation(s);
and
(B) the vantage point from
which the crawl space was inspected; and
(3) generally report present
and visible indications used to render the opinion of adverse performance,
such as:
(A) open or offset concrete
cracks;
(B) binding, out-of-square,
nonlatching, warped, or twisted doors or frames;
(C) framing or frieze board
separations;
(D) out-of-square wall
openings or separations at wall openings or between the cladding and
window/door frames;
(E) sloping floors,
countertops, cabinet doors, or window/door casings;
(F) wall, floor, or ceiling
cracks;
(G) rotating, buckling,
cracking, or deflecting masonry cladding;
(H) separation of walls from
ceilings or floors; and
(I) soil erosion, subsidence
or shrinkage adjacent to the foundation and differential movement of
abutting flatwork such as walkways, driveways, and patios;
(4) report as Deficient:
(A) exposed or damaged
reinforcement;
(B) a crawl space that does
not appear to be adequately ventilated;
(C) crawl space drainage that
does not appear to be adequate;
(D) deteriorated materials;
(E) damaged beams, joists,
bridging, blocking, piers, posts, pilings, or subfloor;
(F) non-supporting piers,
posts, pilings, columns, beams, sills, or joists; and
(G) damaged retaining walls
related to foundation performance; and
(5) render a written opinion as
to the performance of the foundation.
(b)
Specific limitations for foundations. The inspector is not required to: top
(1) enter a crawlspace or any
area where headroom is less than 18 inches or the access opening is less than
24 inches wide and 18 inches high;
(2) provide an exhaustive list of
indicators of possible adverse performance; or
(3) inspect retaining walls not
related to foundation performance.
(c)
Grading and drainage. The inspector shall
report as Deficient:
top
(1) improper or
inadequate grading around the foundation (including flatwork);
(2) erosion;
(3) water ponding; and
(4) deficiencies in installed
gutter and downspout systems.
(d) Specific limitations for
grading and drainage. The inspector is not required to:
top
(1) inspect flatwork or
detention/retention ponds (except as related to slope and drainage);
(2) determine area hydrology or the
presence of underground water; or
(3) determine the efficiency or
operation of underground or surface drainage systems.
(e) Roof covering materials. The
inspector shall:
top
(1) inspect the roof covering
materials from the surface of the roof;
(2) report:
(A) type of roof covering (s);
(B) vantage point from where the
roof was inspected
(C) any levels or surfaces that
were not accessed;
(D) evidence of previous repairs
to roof covering materials, flashing details, skylights, and other roof
penetrations; and
(E) evidence of water
penetration; and
(3) report as Deficient:
(A) a roof covering that is not
appropriate for the slope of the roof;
(B) deficiencies in:
(i) fastening of roof covering
material, as determined by a random sampling;
(ii) roof covering materials;
(iii) flashing details;
(iv) skylights; and
(v) other roof penetrations.
(f) Specific limitations for roof
covering. The inspector is not required to:
top
(1) determine the remaining life
expectancy of the roof covering;
(2) inspect the roof from the roof
level if, in the inspector’s reasonable judgment, the inspector cannot safely
reach or stay on the roof or significant damage to the roof covering materials
may result from walking on the roof;
(3) determine the number of layers
of roof covering material;
(4) identify latent hail damage; or
(5) provide an exhaustive list of
locations of water penetrations or previous repairs.
(g) Roof structure and attic. The
inspector shall:
top
(1) report:
(A) the vantage point from which
the attic space was inspected;
(B) the presence of and
approximate average depth of attic insulation and thickness of vertical
insulation, when visible; and
(C) evidence of water
penetration; and
(2) report as Deficient:
(A) attic space that does not
appear to be adequately ventilated;
(B) deficiencies in installed
framing members and decking;
2010-01-02-4 prior fire history silver paint
top
(C) deflections or depressions in
the roof surface as related to the adverse performance of the framing and the
roof deck;
(D) missing insulation;
(E) deficiencies in attic access
ladder and access opening; and
(F) deficiencies in attic
ventilators.
(h) Specific limitations for roof
structure and attic. The inspector is not required to:
top
(1) enter attics or unfinished
spaces where openings are less than 22 inches by 30 inches or headroom is less
than 30 inches;
(2) operate powered ventilators; or
(3) provide an exhaustive list of
locations of water penetrations.
(i)
Interior walls, ceilings, floors, and doors. The inspector shall:
top
(1) report evidence of water
penetration; and
(2) report as Deficient:
(A) doors and hardware that do
not operate properly;
(B) deficiencies related to
structural performance or water penetration; and
(C) lack of fire separation
between the garage and the residence and its attic space.
(j) Specific limitation for interior walls, doors,
ceilings, and floors. The inspector is not required to:
top
(1) report cosmetic damage or the
condition of floor, wall, or ceiling coverings; paints, stains, or other surface
coatings; cabinets; or countertops, or
(2) provide an exhaustive list of
locations of water penetrations.
(k)
Exterior walls, doors, and windows. The inspector shall:
top
(1) report evidence of water
penetration; and
(2) report as
Deficient:
(A) the lack of functional
emergency escape and rescue openings in all sleeping rooms;
(B) the lack of a solid wood door
not less than 1-3/8 inches in thickness, a solid or honeycomb core steel door
not less than 1-3/8 inches thick, or a 20-minute fire-rated door between the
residence and an attached garage;
(C) missing or damaged screens;
(D) deficiencies related to
structural performance or water penetration; and
(E) deficiencies in:
(i) claddings;
2010-01-02-2 weepholes over lintels status
top
(ii) water resistant materials
and coatings;
(iii) flashing details and
terminations;
(iv) the condition and operation
of exterior doors, garage doors, and hardware; and
(v) window operation and
components.
(l) Specific limitations for
exterior walls, doors, and windows. The inspector is not required to:
top
(1) report the condition or
presence of awnings, shutters, security devices, or systems;
(2) determine the cosmetic condition of paints, stains, or other surface
coatings; or
(3) operate a lock if the key is
not available.
(m) Exterior and interior
glazing. The inspector shall:
top
(1) inspect the window and door
glazing; and
(2) report as Deficient:
(A) insulated
windows that are obviously fogged or display other evidence of broken seals;
(B) deficiencies in glazing,
weather stripping, and glazing compound in windows and exterior doors; and
(C) the absence of safety glass
in hazardous locations.
(n) Specific limitation for
exterior and interior glazing. The inspector is not required to:
top
(1) exhaustively observe insulated
windows for evidence of broken seals;
(2) exhaustively observe glazing
for identifying labels; or
(3) identify specific locations of
damage.
(o) Interior
and exterior stairways. The inspector shall report as Deficient:
top
(1) spacing
between intermediate balusters, spindles, or rails for steps, stairways, guards,
and railings that permit passage of an object greater than 4 inches in diameter,
except that on the open side of the staircase treads, spheres less than 4-3/8
inches in diameter may pass through the guard rail balusters or spindles; and
2010-01-02-9 stair balustrade spacing
top
(2) deficiencies in steps,
stairways, landings, guardrails, and handrails.
2010-01-02-6 stair headroom
top
(p) Specific
limitation for stairways. The inspector is not required to exhaustively measure
every stairway component.
top
(q) Fireplace
and chimney. The inspector shall report as Deficient:
top
(1) built-up creosote in visible
areas of the firebox and flue;
(2) the presence of combustible
materials in near proximity to the firebox opening;
(3) the absence of
fireblocking at the attic penetration of the chimney flue, where accessible;
(4) an inoperative circulating
fan; and
(5) deficiencies in the:
(A) damper;
2010-01-02-1 fireplace damper clamp
top
(B) lintel, hearth, hearth
extension, and firebox;
(C) gas log lighter valve and
location;
(D) combustion air vents; and
(E) chimney structure,
termination, coping, crown, caps, and spark arrestor.
(r) Specific limitations for
fireplace and chimney. The inspector is not required to:
top
(1) verify the integrity of the
flue;
(2) perform a chimney smoke test;
or
(3) determine the adequacy of the
draft.
(s) Porches,
Balconies, Decks, and Carports. The inspector shall:
top
(1) inspect balconies, attached
carports, and attached porches and abutting porches, decks, and balconies that
are used for ingress and egress; and
(2) report as Deficient:
(A) on decks 30 inches or higher
above the adjacent grade, spacings between intermediate balusters, spindles, or
rails that permit passage of an object greater than four inches in diameter;
(B) deficiencies in visible
footings, piers, posts, pilings, beams, joists, decking, water proofing at
interfaces, flashing, surface coverings, and attachment points of porches,
decks, balconies, and carports; and
(C) deficiencies in, or absence
of required, guardrails and handrails.
(t) Specific limitation for
porches, balconies, decks, and carports. The inspector is not required to:
top
(1) exhaustively
measure the porch, balcony, deck, or attached carport components; or
(2) enter any area where headroom
is less than 18 inches or the access opening is less than 24 inches wide and 18
inches high.
§535.229. Standards of Practice:
Minimum Inspection Requirements for Electrical Systems.
(a) Service
entrance and panels. The inspector shall report as Deficient:
top
(1) a drop, weatherhead, or mast
that is not securely fastened to the structure;
(2) the lack of a grounding
electrode system;
(3) the lack of a grounding
electrode conductor;
(4) the lack of a secure
connection to the grounding electrode system;
(5) deficiencies in the
insulation of the service entrance conductors, drip loop, separation of
conductors at weatherheads, and clearances;
(6) electrical cabinets, gutters,
meter cans, and panel boards that:
(A) are not secured to the
structure;
(B) are not appropriate for their
location;
(C) have deficiencies in
clearances and accessibility;
(D) are missing knockouts; or
(E) are not bonded and grounded;
(7) cabinets, disconnects, cutout
boxes, and panel boards that do not have dead fronts secured in place with
proper fasteners;
(8) conductors not protected from
the edges of electrical cabinets, gutters, or cutout boxes;
(9) trip ties not installed on
240 volt circuits;
(10) deficiencies in the type and
condition of the wiring in the cutout boxes, cabinets, or gutters;
2010-01-02-3 double tab neutral
top
(11) deficiencies in the
compatibility of overcurrent devices and conductors;
(12) deficiencies in the
overcurrent device and circuit for labeled and listed 240 volt appliances;
(13) a panel that is installed in
a hazardous location, such as a clothes closet, a bathroom, where there are
corrosive or easily ignitable materials, or where the panel is exposed to
physical damage;
(14) the absence of appropriate
connections, such as copper/aluminum approved devices;
(15) the absence of anti-oxidants
on aluminum conductor terminations;
(16) the lack of a main
disconnecting means;
(17) the lack of arc-fault
circuit interrupting devices serving family rooms, dining rooms, living rooms,
parlors, libraries, dens, bedrooms, sunrooms, recreations rooms, closets,
hallways, or similar rooms or areas; and
(18) failure of operation of
installed arc fault circuit interrupter devices.
(b) Specific limitations for
service entrance and panels. The inspector is not required to:
top
(1) determine present or future
sufficiency of service capacity amperage, voltage, or the capacity of the
electrical system;
(2) test arc-fault circuit
interrupter devices when the property is occupied or damage to personal property
may result, in the inspector’s reasonable judgment;
(3) report the lack of arc-fault
circuit interrupter protection when the circuits are in conduit;
(4) conduct voltage drop
calculations;
(5) determine the accuracy of
overcurrent device labeling;
(6) remove covers where hazardous
as judged by the inspector;
(7) verify the effectiveness of
overcurrent devices; or
(8) operate overcurrent devices.
(c) Branch
circuits, connected devices, and fixtures. The inspector shall:
top
(1) report the type of branch
circuit conductors;
(2) manually test the accessible
smoke alarms by use of the manufacturer’s approved test or by the use of canned
smoke; and
(3) report as Deficient:
(A) the lack of ground-fault
circuit interrupter protection in all:
(i) bathroom receptacles;
(ii) garage receptacles;
(iii) outdoor receptacles;
(iv) crawl space receptacles;
(v) unfinished basement
receptacles;
(vi) kitchen countertop
receptacles; and
(vii) laundry, utility, and wet
bar sink receptacles located within 6 feet of the outside edge of a laundry,
utility, or wet bar sink; and
(B) the failure of operation of
ground-fault circuit interrupter protection devices;
(C) receptacles that:
(i) are damaged;
(ii) are inoperative;
(iii) have incorrect polarity;
(iv) are not grounded, if
applicable;
(v) display evidence of arcing or
excessive heat;
(vi) are not securely mounted; or
(vii) have missing or damaged
covers;
(D) switches that:
(i) are damaged;
(ii) are inoperative;
(iii) display evidence of arcing
or excessive heat;
(iv) are not securely mounted; or
(v) have missing or damaged
covers;
(E) deficiencies in or absences
of conduit, where applicable;
(F) appliances and metal pipes
that are not bonded or grounded;
(G) deficiencies in wiring,
wiring terminations, junctions, junction boxes, devices, and fixtures, including
improper location;
(H) the lack of equipment
disconnects;
(I) the absence of appropriate
connections, such as copper/aluminum approved devices, if branch circuit
aluminum conductors are discovered in the main or subpanel based on a random
sampling of accessible receptacles and switches;
(J) improper use of extension
cords;
(K) deficiencies in
smoke alarms that are not connected to a central alarm
system; and
top
(L) the lack of smoke alarms:
(i) in each sleeping room;
(ii) outside each separate
sleeping area in the immediate vicinity of the sleeping rooms; and
(iii) on each additional story of
the dwelling, including basements but excluding crawl spaces and uninhabitable
attics (in dwellings with split levels and without an intervening door between
the levels, a smoke alarm installed on the upper level and the adjacent lower
level shall suffice provided that the lower level is less than one full story
below the upper level).
(d) Specific limitations for branch
circuits, connected devices, and fixtures. The inspector is not required to:
top
(1) inspect low voltage wiring;
(2) disassemble mechanical
appliances;
(3) verify the effectiveness of
smoke alarms;
(4) verify interconnectivity of
smoke alarms
(5) activate smoke alarms that are
being actively monitored or require the use of codes; or
(6) verify that smoke alarms are
suitable for the hearing-impaired.
§535.230. Standards of Practice:
Minimum Inspection Requirements for Heating, Ventilation, and Air Conditioning
Systems.
(a)
Heating equipment. The inspector shall:
top
(1) report:
(A) the type of heating system
(s); and
(B) the energy source (s);
(2) report as Deficient:
(A) an inoperative unit;
(B) deficiencies in the controls
and operating components of the system;
(C) the lack of protection from
physical damage;
(D) burners, burner ignition
devices or heating elements, switches, and thermostats that are not a minimum of
18 inches above the lowest garage floor elevation, unless the unit is listed for
garage floor installation;
(E) inappropriate location;
(F) inadequate access and
clearances;
(G) deficiencies in mounting and
operation of window units; and
(H) deficiencies in thermostats;
(3) in electric units, report as
Deficient deficiencies in:
(A) operation of heating
elements; and
(B) condition of conductors; and
(4) in gas units, report as
Deficient:
(A) gas leaks;
(B) the presence of forced air in
the burner compartment;
(C) flame impingement, uplifting
flame, improper flame color, or excessive scale buildup;
(D) the lack of a gas shut-off
valve; and
(E) deficiencies in:
(i) conditioned, combustion, and
dilution air;
(ii) gas shut-off valves and
locations;
(iii) gas connector materials and
connections; and
2010-01-02-10 copper gas line
top
2010-01-02-11 flex line connectors
(iv) the vent pipe, draft hood,
draft, proximity to combustibles, and vent termination point and clearances.
2010-01-02-5 tape on Type B
top
2010-01-02-7 transite pipe
(b)
Cooling equipment other than evaporative coolers. The inspector shall:
top
(1) report the type of system
(s); and
(2) report as Deficient:
(A) inoperative unit (s);
(B) inadequate cooling as
demonstrated by its performance in the reasonable judgment of the inspector;
(C) inadequate access and
clearances;
(D) noticeable vibration of the
blower fan or condensing fan;
(E) deficiencies in the
condensate drain and auxiliary/secondary pan and drain system;
(F) water in the
auxiliary/secondary drain pan;
(G) a primary drain pipe that
terminates in a sewer vent;
(H) missing or deficient
refrigerant pipe insulation;
(I) dirty evaporator or
condensing coils, where accessible;
(J) damaged casings on the coils;
(K) a condensing unit lacking
adequate clearances or air circulation or that has deficiencies in the condition
of fins, location, levelness, or elevation above ground surfaces;
(L) deficiencies in mounting and
operation of window or wall units; and
(M) deficiencies in thermostats.
(c)
Evaporative coolers. The inspector shall:
top
(1) report:
(A) type of system (s) (one- or
two speed);
(B) the type of water supply
line; and
(C) winterized units that are
drained and shut down; and
(2) report as Deficient:
(A) inoperative units;
(B) inadequate access and
clearances;
(C) corrosive and mineral
build-up or rust damage/decay at the pump, louvered panels, water trays,
exterior housing, or the roof frame;
(D) less than a one-inch air gap
between the water discharge at the float and water level in the reservoir;
(E) corrosion, decay, or rust on
the pulleys of the motor or blower;
(F) the lack of a damper; and
(G) deficiencies in the:
(i) function of the pump;
(ii) interior housing, the spider
tubes, tube clips, bleeder system;
(iii) blower and bearings;
(iv) float bracket;
(v) fan belt;
(vi) evaporative pad (s);
(vii) installation and condition
of the legs on the roof rails and fasteners to the roof structure and the unit;
(viii) roof jack; and
(ix) thermostats.
(d) Duct system,
chases, and vents. The inspector shall report as Deficient:
top
(1) damaged ducting or
insulation, improper material, or improper routing of ducts;
(2) the absence of air flow at
accessible supply registers in the habitable areas of the structure;
(3) improper or inadequate
clearance from the earth; and
(4) deficiencies in:
(A) duct fans;
(B) filters;
(C) grills or registers;
(D) the location of return air
openings; and
(E) gas piping, sewer vents,
electrical wiring, or junction boxes in the duct system, plenum (s), and chase
(s).
(e) Specific
limitations for the heating equipment, cooling equipment, duct system, chases,
and vents. The inspector is not required to:
top
(1) program digital thermostats or
controls;
(2) inspect:
(A) for pressure of the system
refrigerant, type of refrigerant, or refrigerant leaks;
(B) winterized evaporative coolers;
or
(C) humidifiers, dehumidifiers, air
purifiers, motorized dampers, electronic air filters, multi-stage controllers,
sequencers, heat reclaimers, wood burning stoves, boilers, oil-fired units,
supplemental heating appliances, de-icing provisions, or reversing valves;
(3) operate:
(A) setback features on thermostats
or controls;
(B) cooling equipment when the
outdoor temperature is less than 60 degrees Fahrenheit;
(C) radiant heaters, steam heat
systems, or unvented gas-fired heating appliances; or
(D) heat pumps when temperatures
may damage equipment;
(4) verify:
(A) compatibility of components;
(B) the accuracy of thermostats; or
(C) the integrity of the heat
exchanger; or
(5) determine:
(A) sizing, efficiency, or adequacy
of the system;
(B) uniformity of the supply of
conditioned air to the various parts of the structure; or
(C) types of materials contained in
insulation.
§535.231. Standards of Practice:
Minimum Inspection Requirements for Plumbing Systems.
(a)
Plumbing systems. The inspector shall:
top
(1) report:
(A) static water pressure;
(B) location of water meter; and
(C) location of main water supply
valve; and
(2) report as Deficient:
(A) the presence of active leaks;
(B) the lack of fixture shut-off
valves;
(C) the lack of dielectric
unions, when applicable;
(D) the lack of back-flow
devices, anti-siphon devices, or air gaps at the flow end of fixtures;
(E) water pressure below 40 psi
or above 80 psi static;
(F) the lack of a pressure
reducing valve when the water pressure exceeds 80 PSI;
(G) the lack of an expansion tank
at the water heater (s) when a pressure reducing valve is in place at the water
supply line/system; and
(H) deficiencies in:
(i) water supply pipes and waste
pipes;
(ii) the installation and
termination of the vent system;
(iii) the operation of fixtures
and faucets not connected to an appliance;
(iv) water supply, as determined
by viewing functional flow in two fixtures operated simultaneously;
(v) functional drainage at
fixtures;
2009-12-19-1 shower residual water
top
(vi) orientation of hot and cold
faucets;
(vii) installed mechanical drain
stops;
(viii) installation, condition,
and operation of commodes;
(ix) fixtures, showers, tubs, and
enclosures; and
(x) the condition of the gas
distribution system.
(b) Specific limitations for
plumbing systems. The inspector is not required to:
top
(1) operate any main, branch, or
shutoff valves;
(2) operate or inspect sump pumps
or waste ejector pumps;
(3) inspect:
(A) any system that has been
winterized, shut down or otherwise secured;
(B) circulating pumps,
free-standing appliances, solar water heating systems, water conditioning
equipment, filter systems, water mains, private water supply systems, water
wells, pressure tanks, sprinkler systems, swimming pools, or fire sprinkler
systems;
(C) the inaccessible gas supply
system for leaks;
(D) for sewer clean-outs; or
(E) for the presence or operation
of private sewage disposal systems;
(4) determine:
(A) quality, potability, or volume
of the water supply; or
(B) effectiveness of backflow or
anti siphon devices; or
(5) verify the functionality of
clothes washing drains or floor drains.
(c) Water
heaters. The inspector shall:
top
(1) report the energy source;
(2) report the capacity of the
unit (s);
(3) report as Deficient:
(A) inoperative unit (s);
(B) leaking or corroded fittings
or tank (s);
(C) broken or missing parts or
controls;
(D) the lack of a cold water
shut-off valve;
(E) if applicable, the lack of a
pan and drain system and the improper termination of the pan drain line;
2010-01-02-8 water heater combo tp drain
top
(F) an unsafe location;
(G) burners, burner ignition
devices or heating elements, switches, or thermostats that are not a minimum of
18 inches above the lowest garage floor elevation, unless the unit is listed for
garage floor installation;
(H) inappropriate location;
(I) inadequate access and
clearances;
(J) the lack of protection from
physical damage;
(K) a temperature and pressure
relief valve that:
(i) does not operate manually;
(ii) leaks;
(iii) is damaged;
(iv) cannot be tested due to
obstructions;
(v) is corroded; or
(vi) is improperly located; and
(L) temperature and pressure
relief valve discharge piping that:
(i) lacks gravity drainage;
(ii) is improperly sized;
(iii) has inadequate material; or
(iv) lacks proper termination;
(4) in electric units, report as
Deficient deficiencies in:
(A) operation of heating
elements; and
(B) condition of conductors; and
(5) in gas units, report as
Deficient:
(A) gas leaks;
(B) lack of burner shield (s);
(C) flame impingement, uplifting
flame, improper flame color, or excessive scale build-up;
(D) the lack of a gas shut-off
valve; and
(E) deficiencies in:
(i) combustion and dilution air;
(ii) gas shut-off valve (s) and
location (s);
(iii) gas connector materials and
connections; and
2010-01-02-10 copper gas line
top
2010-01-02-11 flex line connectors
(iv) vent pipe, draft hood,
draft, proximity to combustibles, and vent termination point and clearances.
2010-01-02-5 tape on Type B
top
2010-01-02-7 transite pipe
(d) Specific limitations for water
heaters. The inspector is not required to:
top
(1) verify the effectiveness of the
temperature and pressure relief valve, discharge piping, or pan drain pipes;
(2) operate the temperature and
pressure relief valve if the operation of the valve may, in the inspector’s
reasonable judgment, cause damage to persons or property; or
(3) determine the efficiency or
adequacy of the unit.
(e) Hydro-massage
therapy equipment. The inspector shall report as Deficient:
top
(1) inoperative unit (s) and
controls;
(2) the presence of active leaks;
(3) inaccessible pump (s) or
motor (s);
(4) the lack or failure of
required ground-fault circuit interrupter protection; and
(5) deficiencies in the ports,
valves, grates, and covers.
(f) Specific
limitation for hydro-massage therapy equipment. The inspector is not required to
determine the adequacy of self draining features of circulation systems.
top
§535.232. Standards of Practice:
Minimum Inspection Requirements for Appliances.
(a)
Dishwasher. The inspector shall report as Deficient:
top
RFI about cord
(1) inoperative unit (s);
(2) rust on the interior of the
cabinet or components;
(3) failure to drain properly;
(4) the presence of active water
leaks; and
(5) deficiencies in the:
(A) door gasket;
(B) control and control panels;
(C) dish racks;
(D) rollers;
(E) spray arms;
(F) operation of the soap
dispenser;
(G) door springs;
(H) dryer element;
(I) door latch and door
disconnect;
(J) rinse cap;
(K) secure mounting of the unit;
and
(L) backflow prevention.
(b) Food waste
disposer. The inspector shall report as Deficient:
top
(1) inoperative unit (s);
(2) unusual sounds or vibration
level;
(3) the presence of active water
leaks; and
(4) deficiencies in the:
(A) splash guard;
(B) grinding components;
(C) exterior casing; and
(D) secure mounting of the unit.
(c) Range
exhaust vent. The inspector shall report as Deficient:
top
(1) inoperative unit (s);
(2) a vent pipe that does not
terminate outside the structure, if the unit is not of a recirculating type or
configuration;
(3) inadequate vent pipe
material;
(4) unusual sounds or vibration
levels from the blower fan (s);
(5) blower (s) that do not
operate at all speeds; and
(6) deficiencies in the:
A) filter;
(B) vent pipe;
(C) light and lens;
(D) secure mounting of the unit;
and
(E) switches.
(d) Electric or
gas ranges, cooktops, and ovens. The inspector shall report as Deficient:
top
(1) inoperative unit (s);
(2) the lack of a gas shut-off
valve;
(3) gas leaks; and
(4) deficiencies in the:
(A) controls and control panels;
(B) thermostat (s) sensor
support;
(C) glass panels;
(D) door gasket (s), hinges,
springs, closure, and handles;
(E) door latch;
(F) heating elements or burners;
(G) thermostat accuracy (within
25 degrees at a setting of 350 °F);
(H) drip pans;
(I) lights and lenses;
(J) clearance to combustible
material;
(K) anti-tip device;
(L) gas shut-off valve (s) and
location (s);
(M) gas connector materials and
connections; and
(N) secure mounting of the unit.
(e) Microwave
oven. The inspector shall:
top
(1) inspect built-in units; and
(2) report as Deficient:
(A) inoperative unit (s); and
(B) deficiencies in the:
(i) controls and control panels;
(ii) handles;
(iii) the turn table;
(iv) interior surfaces;
(v) door and door seal;
(vi) glass panels;
(vii) lights and lenses;
(viii) secure mounting of the
unit; and
(ix) operation, as determined by
heating a container of water or with other means of testing.
(f) Trash
compactor. The inspector shall report as Deficient:
top
(1) inoperative unit (s);
(2) unusual sounds or vibration
levels; and
(3) deficiencies in the secure
mounting of the unit.
(g) Mechanical
exhaust vents and bathroom heaters. The inspector shall report as Deficient:
top
(1) inoperative unit (s);
(2) unusual sounds, speed, and
vibration levels;
(3) vent pipes that do not
terminate outside the structure;
(4) a gas heater that is not
vented to the exterior of the structure; and
(5) the lack of an exhaust
ventilator in required areas.
2009-12-19-2 exhaust venting in required areas
top
(h)
Garage door operators. The inspector shall report as Deficient:
top
(1) inoperative unit (s);
(2) door locks or side ropes that
have not been removed or disabled; and
(3) deficiencies in:
(A) installation;
(B) condition and operation of
the garage door operator;
(C) automatic reversal during the
closing cycle;
(D) electronic sensors;
(E) the control button; and
(F) the emergency release
components.
(i) Doorbell
and chimes. The inspector shall report as Deficient:
top
(1) inoperable unit (s); and
(2) deficiencies in components.
(j) Dryer vents. The inspector
shall report as Deficient:
top
(1) improper routing and length
of vent pipe;
(2) inadequate vent pipe
material;
(3) improper termination;
(4) the lack of a dryer vent
system when provisions are present for a dryer; and
(5) damaged or missing exterior
cover.
(k) Specific limitations for
appliances. The inspector is not required to:
top
(1) operate or determine the
condition of other auxiliary components of inspected items;
(2) test for microwave oven
radiation leaks;
(3) inspect self-cleaning
functions;
(4) test trash compactor ram
pressure; or
(5) determine the adequacy of
venting systems.
§535.233. Standards of Practice:
Minimum Inspection Requirements for Optional Systems.
If an inspector
agrees to inspect a component described in this section, §535.227 of this title
relating to Standards of Practice: General Provisions and the applicable
provisions below apply.
(1) Lawn and garden sprinkler
systems. The inspector shall:
top
(A) manually operate all zones or
stations on the system; and
(B) report as Deficient:
(i) surface water leaks;
(ii) the absence or improper
installation of anti-siphon devices and backflow preventers;
(iii) the absence of shut-off
valves;
(iv) deficiencies in water flow
or pressure at the zone heads;
(v) the lack of a rain or freeze
sensor;
(vi) deficiencies in the
condition of the control box; and
(vii) deficiencies in the
operation of each zone, associated valves, and spray head patterns.
(2) Specific limitations for lawn
and garden sprinkler systems. The inspector is not required to inspect:
top
(A) for effective coverage of the
sprinkler system;
(B) the automatic function of the
timer or control box;
(C) the effectiveness of the rain
or freeze sensor; or
(D) sizing and effectiveness of
anti siphon devices or backflow preventers.
(3) Swimming pools, spas, hot
tubs, and equipment. The inspector shall:
top
(A) report the type of
construction;
(B) report as Deficient:
(i) a pump motor, blower, or
other electrical equipment that lacks bonding;
(ii) the absence of or
deficiencies in safety barriers;
(iii) water leaks in above-ground
pipes and equipment;
(iv) deficiencies in lighting
fixture (s);
(v)the lack or failure of
required ground-fault circuit interrupter protection; and
(vi) deficiencies in:
(I) surfaces;
(II) tiles, coping, and decks;
(III) slides, steps, diving
boards, handrails, and other equipment;
(IV) drains, skimmers, and
valves; and
(V) filters, gauges, pumps,
motors, controls, and sweeps; and
(C) when inspecting a pool
heater, report deficiencies that these standards of practice require to be
reported for the heating system.
(4) Specific limitations for
swimming pools, spas, hot tubs, and equipment. The inspector is not required to:
top
(A) dismantle or otherwise open any
components or lines;
(B) operate valves;
(C) uncover or excavate any lines
or concealed components of the system or determine the presence of sub-surface
leaks;
(D) fill the pool, spa, or hot tub
with water;
(E) inspect any system that has
been winterized, shut down, or otherwise secured;
(F) determine the presence of
subsurface water tables; or
(G) inspect ancillary equipment
such as computer controls, covers, chlorinators or other chemical dispensers, or
water ionization devices or conditioners other than required by this section.
(5) Outbuildings. The inspector
shall report as Deficient:
top
(A) the lack of ground-fault
circuit interrupter protection in grade-level portions of unfinished accessory
buildings used for storage or work areas, boathouses, and boat hoists; and
(B) deficiencies in the
structural, electrical, plumbing, heating, ventilation, and cooling systems that
these standards of practice require to be reported for the principal structure.
(6) Outdoor cooking equipment.
The inspector shall:
top
(A) inspect the built-in
equipment; and
(B) report the energy source; and
(C) report as Deficient:
(i) inoperative unit (s);
(ii) a unit or pedestal that is
not stable;
(iii) gas leaks; and
(iv) deficiencies in:
(I) operation;
(II) control knobs, handles,
burner bars, grills, the box, the rotisserie (if present), and heat diffusion
material;
(III) gas shut-off valve (s) and
location (s); and
(IV) gas connector materials and
connections.
(7) Gas supply systems. The
inspector shall:
top
(A) test gas lines using a local
or an industry-accepted procedure; and
(B) report as Deficient:
(i) leaks; and
(ii) deficiencies in the
condition and type of gas piping, fittings, and valves.
2010-01-02-10 copper gas line
top
2010-01-02-11 flex line connectors
(8) Specific
limitation for gas lines. The inspector is not required to inspect sacrificial
anode bonding or for its existence.
top
(9) Private water wells. The
inspector shall:
top
(A) operate at least two fixtures
simultaneously;
(B) recommend or arrange to have
performed water quality or potability testing;
(C) report:
(i) the type of pump and storage
equipment; and
(ii) the proximity of any known
septic system; and
(D) report as Deficient
deficiencies in:
(i) water pressure and flow and
operation of pressure switches;
(ii) the condition of visible and
accessible equipment and components; and
(iii) the well head, including
improper site drainage and clearances.
(10) Specific limitations for
private water wells. The inspector is not required to:
top
(A) open, uncover, or remove the
pump, heads, screens, lines, or other components or parts of the system;
(B) determine the reliability of
the water supply or source; or
(C) locate or verify underground
water leaks.
(11) Private sewage disposal
(septic) systems. The inspector shall:
top
(A) report:
(i) the type of system;
(ii) the location of the drain
field; and
(iii) the proximity of any known
water wells, underground cisterns, water supply lines, bodies of water, sharp
slopes or breaks, easement lines, property lines, soil absorption systems,
swimming pools, or sprinkler systems; and
(B) report as Deficient:
(i) visual or olfactory evidence
of effluent seepage or flow at the surface of the ground;
(ii) inoperative aerators or
dosing pumps; and
(iii) deficiencies in:
(I) accessible or visible
components;
(II) functional flow;
(III) site drainage and
clearances around or adjacent to the system; and
(IV) the aerobic discharge
system.
(12) Specific limitations for
individual private sewage disposal (septic) systems. The inspector is not
required to:
top
(A) excavate or uncover the system
or its components;
(B) determine the size, adequacy,
or efficiency of the system; or
(C) determine the type of
construction used.
(13) Whole-house vacuum system.
The inspector shall report as Deficient:
top
(A) inoperative units;
(B) deficiencies in the main
unit; and
(C) deficiencies in outlets.
(14) Specific limitations for
whole-house vacuum systems. The inspector is not required to:
top
(A) inspect the attachments or
hoses; or
(B) verify that
accessory components are present.
(15) Other built-in appliances.
The inspector shall report deficiencies in condition or operation of other
built-in appliances not listed in this section.
top